EasyManua.ls Logo

INVT GD350-011G-4

INVT GD350-011G-4
341 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350 series high-performance multi-function inverter Chapter 5
-61-
Function
code
Name
Detailed parameter description
Default
value
P04.07
V/F frequency point 3 of
motor 1
P04.05 P02.02 or P04.05 P02.16
0.00Hz
P04.08
V/F voltage point 3 of motor 1
0.0%110.0%
0.0%
P04.09
V/F slip compensation gain of
motor 1
0.0200.0%
100.0%
P04.10
Low-frequency oscillation
control factor of motor 1
0100
10
P04.11
High-frequency oscillation
control factor of motor 1
0100
10
P04.12
Oscillation control threshold
of motor 1
0.00HzP00.03 (max. output frequency)
30.00Hz
P04.13
V/F curve setup of motor 2
0: Straight V/F curve;
1: Multi-point V/F curve
2: Torque-down V/F curve (1.3
th
order)
3: Torque-down V/F curve (1.7
th
order)
4: Torque-down V/F curve (2.0
th
order)
5: Customize V/F (V/F separation)
0
P04.14
Torque boost of motor 2
0.0%: (automatic) 0.1%10.0%
0.0%
P04.15
Motor 2 torque boost cut-off
0.0%50.0% (rated frequency of motor 1)
20.0%
P04.16
V/F frequency point 1 of
motor 2
0.00HzP04.18
0.00Hz
P04.17
V/F voltage point 1 of motor 2
0.0%110.0%
0.0%
P04.18
V/F frequency point 2 of
motor 2
P04.16 P04.20
0.00Hz
P04.19
V/F voltage point 2 of motor 2
0.0%110.0%
0.0%
P04.20
V/F frequency point 3 of
motor 2
P04.18 P02.02 or P04.18 P02.16
0.00Hz
P04.21
V/F voltage point 3 of motor 2
0.0%110.0%
0.0%
P04.22
V/F slip compensation gain of
motor 2
0.0200.0%
100.0%
P04.23
Low-frequency oscillation
control factor of motor 2
0100
10
P04.24
High-frequency oscillation
control factor of motor 2
0100
10
P04.25
Oscillation control threshold
of motor 2
0.00HzP00.03 (max. output frequency)
30.00Hz
P04.26
Energy-saving run
0: No
1: Automatic energy-saving run
0

Table of Contents

Related product manuals