Goodrive350 series high-performance multi-function inverter  Appendix D 
-314- 
reduces grounding resistance, and thus improves impedance continuity. 
To  effectively  restrict  the  emission  and  conduction  of  radio  frequency  (RF)  interference,  the 
conductivity of the shielded cable must at least be 1/10 of the conductivity of the phase conductor. 
This requirement can be well met by a copper or aluminium shield layer. The following figure shows 
the  minimum  requirement  on  motor  cables  of  an  inverter.  The  cable  must  consist  of  a  layer  of 
spiral-shaped copper strips. The denser the shield layer is, the more effectively the electromagnetic 
interference is restricted. 
Cross-section of the cable 
Insulating layer 
Shield layer 
 
D.4.2 Control cables 
All analog control cables and cables used for frequency input must be shielded cables. Analog signal 
cables need  to  be  double-shielded twisted-pair cables  (as shown  in  figure a).  Use  one separate 
shielded twisted pair for each signal. Do not use the same ground wire for different analog signals. 
Power cable arrangement
 
Multiple double-shielded twisted-pair cables
 
Multiple shielded twisted-pair cables
 
 
For low-voltage digital signals, double-shielded cables are recommended, but shielded or unshielded 
twisted pairs (as shown in figure b) also can be used. For frequency signals, however, only shielded 
cables can be used. 
Relay cables need to be those with metal braided shield layers. 
Keypads  need  to  be  connected  by  using  network  cables.  In  complicated  electromagnetic 
environments, shielded network cables are recommended. 
Note:  Analog signals  and  digital signals  cannot  use  the same cables,  and  their  cables must  be 
arranged separately. 
Do not perform any voltage endurance or insulation resistance tests, such as high-voltage insulation 
tests or using a megameter to measure the insulation resistance, on the inverter or its components. 
Insulation and voltage endurance tests have been performed between the main circuit and chassis of 
each inverter before delivery. In addition, voltage limiting circuits that can automatically cut off the test 
voltage are configured inside the inverters. 
Note: Check the insulation conditions of the input power cable of an inverter according to the local