Goodrive350 series high-performance multi-function inverter  Chapter 5 
-58- 
(2)  If the torque boost is too large, low-frequency vibration or overcurrent may occur to the motor, if 
such situation occurs, lower the torque boost value. 
Output voltage V
Output frequency f
cut-off
boost
 
2.  Energy-saving run 
During actual running, the inverter can search for the max. efficiency point to keep running in the most 
efficient state to save energy.   
Note:   
(1)  This function is generally used in light load or no-load cases. 
(2)  This function does for fit in cases where load transient is required. 
3.  V/F slip compensation gain 
SVPWM control belongs to open-loop mode, which will cause motor speed to fluctuate when motor 
load  transients.  In  cases  where  strict  speed  requirement  is  needed,  users  can  set  the  slip 
compensation  gain  to  compensate  for  the  speed  variation  caused  by  load  fluctuation  through   
internal output adjustment of inverter. 
The set range of slip compensation gain is 0–200%, in which 100% corresponds to rated slip 
frequency. 
Note: Rated slip frequency= (rated synchronous speed of motor-rated speed of motor) × number of 
motor pole pairs/60 
4.  Oscillation control 
Motor  oscillation  often occurs  in  SVPWM  control  in  large-power  drive  applications.  To  solve  this 
problem, GD350 series inverter sets two function codes to control the oscillation factor, and users can 
set the corresponding function code based on the occurrence frequency of oscillation. 
Note: The larger the set value, the better the control effect, however, if the set value is too large, it 
may easily lead to too large inverter output current. 
Customized V/F curve (V/F separation) function: