Goodrive300-16 special inverter for HVAC Product overview
10
Voltage
degree
Voltage degree
S2: AC 1PH 220V(-15%)~240V(+10%)
2: AC 3PH 220V(-15%)~240V(+10%)
4: AC 3PH 380V(-15%)~440V(+10%)
6: AC 3PH 520V(-15%)~690V(+10%)
Lot number
IP degree
Protective degree (the protective degree
of standard products can be default)
0-IP00;
1-IP20;
2-IP21;
5-IP54;
6-IP65;
Market lot number
HVAC: heating, ventilation and air
conditioning, can be omitted
2.4 Rated specifications
Model
Rated output
power(kW)
Rated input
current(A)
Rated output
current(A)
GD300-16-004G/5R5P-4
4/5.5
13.5/19.5
9.5/14
GD300-16-5R5G/7R5P-4
5.5/7.5
19.5/25
14/18.5
GD300-16-7R5G/011P-4
7.5/11
25/32
18.5/25
GD300-16-011G/015P-4
11/15
32/40
25/32
GD300-16-015G/018P-4
15/18.5
40/47
32/38
GD300-16-018G/022P-4
18.5/22
47/56
38/45
GD300-16-022G/030P-4
22/30
56/70
45/60
GD300-16-030G/037P-4
30/37
70/80
60/75
GD300-16-037G/045P-4
37/45
80/94
75/92
GD300-16-045G/055P-4
45/55
94/128
92/115
GD300-16-055G/075P-4
55/75
128/160
115/150
GD300-16-075G/090P-4
75/90
160/190
150/180
GD300-16-090G/110P-4
90/110
190/225
180/215
GD300-16-110G/132P-4
110/132
225/265
215/260
GD300-16-132G/160P-4
132/160
265/310
260/305
Note:
1. The input current of inverters 4~132kW is detected when the input voltage is 380V and
there is no DC reactors and input/output reactors.
2. The rated output current is defined when the output voltage is 380V.
3. The output current can not exceed the rated output current and the output power can not
exceed the rated output power in the voltage range.