Goodrive300-16 special inverter for HVAC Commissioning guidelines
32
according to the
maintenance
information
Ensure whether there is no
stuff or foreign objects in the
cooling fan and air vent.
Consult the local service representative for more details on the maintenance. Visit the official
website.
3.7 Fault instruction and solution
Do as the following after the inverter fault:
1. Check to ensure there is nothing wrong with the keypad. If not, please contact with the
local INVT office.
2. If there is nothing wrong, please check P07 and ensure the corresponding recorded fault
parameters to confirm the real state when the current fault occurs by all parameters.
3. See the following table for detailed solution and check the corresponding abnormal state.
4. Eliminate the fault and ask for relative help.
5. Check to eliminate the fault and carry out fault reset to run the inverter.
The acceleration is too fast
There is damage to the
internal to IGBT of the phase
The connection of the driving
wires is not good
The grounding is not good
Increase ACC time
Change the power unit
Check the driving wires
Check if there is strong
interference to the external
equipment
The acceleration or
deceleration is too fast
The voltage of the grid is too
low
The power of the inverter is
too low
The load transients or is
Increase the ACC time
Check the input power
Select the inverter with a larger
power
Check if the load is short
circuited (the grounding short
circuited or the wire short