Goodrive300-16 special inverter for HVAC Commissioning guidelines
33
abnormal
The grounding is short
circuited or the output is
phase loss
There is strong external
interference
circuited) or the rotation is not
smooth
Check the output configuration.
Check if there is strong
interference
The input voltage is
abnormal
There is large energy
feedback
Check the input power
Check if the DEC time of the
load is too short or the inverter
starts during the rotation of the
motor or it needs to increase the
energy consumption
components
The voltage of the power
supply is too low
Check the input power of the
supply line
The voltage of the power
supply is too low
The motor setting rated
current is incorrect
The motor stall or load
transients is too strong
Check the power of the supply
line
Reset the rated current of the
motor
Check the load and adjust the
torque lift
The acceleration is too fast
Reset the rotating motor
The voltage of the power
supply is too low.
The load is too heavy.
The motor power is too
small.
Increase the ACC time
Avoid the restarting after
stopping.
Check the power of the supply
line
Select an inverter with bigger
power.
Select a proper motor.
Phase loss or fluctuation of
input R,S,T
Check input power
Check installation distribution