Goodrive300-16 special inverter for HVAC Commissioning guidelines
34
U,V,W phase loss input(or
serious asymmetrical three
phase of the load)
Check the output distribution
Check the motor and cable
Rectifying
module
overheated
Air duct jam or fan damage
Ambient temperature is too
high.
The time of overload running
is too long.
Refer to the overcurrent solution
Redistribute dredge the wind
channel or change the fan
Low the ambient temperature
Check and reconnect
Change the power
Change the power unit
Change the main control panel
SI external fault input
terminals action
Check the external device input
The baud rate setting is
incorrect.
Fault occurs to the
communication wiring.
The communication address
is wrong.
There is strong interference
to the communication.
Set proper baud rate
Check the communication
connection distribution
Set proper communication
address.
Chang or replace the connection
distribution or improve the
anti-interference capability.
The connection of the control
board is not good
Assistant power is bad
Hoare components is broken
The modifying circuit is
abnormal.
Check the connector and
repatch
Change the Hoare
Change the main control panel
The motor capacity does not
comply with the inverter
capability
The rated parameter of the
motor does not set correctly.
Change the inverter mode
Set the rated parameter
according to the motor name
plate
Empty the motor load and