Goodrive300-16 special inverter for HVAC Commissioning guidelines
35
Code
Fault
Cause
Solution
The offset between the
parameters from autotune
and the standard parameter
is huge
Autotune overtime
reidentify
Check the motor connection and
set the parameter.
Check if the upper limit
frequency is above 2/3 of the
rated frequency.
EEP
EEPROM
operation fault
Error of controlling the write
and read of the parameters
Damage to EEPROM
Press STOP/RST to reset
Change the main control panel
bCE
Braking unit
fault
Braking circuit fault or
damage to the braking pipes
The external braking resistor
is not sufficient
Check the braking unit and ,
change new braking pipe
Increase the braking resistor
END
Running time
arrival
The actual running time of
the inverter is above the
internal setting running time.
Ask for the supplier and adjust
the setting running time.
OL3
Electrical
overload
The inverter will report
overload pre-alarm
according to the set value.
Check the load and the overload
pre-alarm point.
PCE
Keypad
communication
fault
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
There is circuit fault on the
communication of the
keypad and main board.
Check the keypad wires and
ensure whether there is mistake.
Check the environment and
avoid the interference source.
Change the hardware and ask
for service.
UPE
Parameters
uploading
fault
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask
for service.