Goodrive300-16 special inverter for HVAC Appendix A
124
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
than P22.47.
P22.48
Emergency
stop
deceleration
time
0.0~600.0s
2.0s
A.3 Goodrive300-16 communication additions
1. MODBUS communication
Function
instruction
Address
definition
Data meaning instruction
R/W
characteristics
Communication
control
command
2000H
0009H: emergency deceleration to stop
W/R
The address of
communication
setting
2002H
PID1 reference 1, range (0~1000, 1000
corresponds to 100.0%)
W/R
2003H
PID1 feedback 1, range (0~1000, 1000
corresponds to 100.0%)
W/R
2009H
Special control command word
Bit6:=1 fire mode enabling
=0: fire mode disabling
Bit7:=1 HVAC invalid enabling
=0: HVAC invalid disabling
Bit8:=1 hibernation triggering enabling
=0: hibernation triggering disabling
Bit9:=1 hibernation waking enabling
=0: hibernation waking disabling
Bit10:=1 PID2 start enabling
=0: PID2 start disabling
Bit11:=1 PID2 stop enabling
=0: PID2 stop disabling
W/R
200FH
PID1 reference 2, range (0~1000, 1000
corresponds to 100.0%)
W/R
2010H
PID1 feedback 2, range (0~1000, 1000
corresponds to 100.0%)
W/R
2011H
PID2 reference, range (0~1000, 1000
W/R