Goodrive300-16 special inverter for HVAC Appendix A
124
Detailed instruction of parameters
Emergency
stop
deceleration
time
A.3 Goodrive300-16 communication additions
1. MODBUS communication
Communication
control
command
0009H: emergency deceleration to stop
The address of
communication
setting
PID1 reference 1, range (0~1000, 1000
corresponds to 100.0%)
PID1 feedback 1, range (0~1000, 1000
corresponds to 100.0%)
Special control command word
Bit6:=1 fire mode enabling
=0: fire mode disabling
Bit7:=1 HVAC invalid enabling
=0: HVAC invalid disabling
Bit8:=1 hibernation triggering enabling
=0: hibernation triggering disabling
Bit9:=1 hibernation waking enabling
=0: hibernation waking disabling
Bit10:=1 PID2 start enabling
=0: PID2 start disabling
Bit11:=1 PID2 stop enabling
=0: PID2 stop disabling
PID1 reference 2, range (0~1000, 1000
corresponds to 100.0%)
PID1 feedback 2, range (0~1000, 1000
corresponds to 100.0%)
PID2 reference, range (0~1000, 1000