Goodrive300-16 special inverter for HVAC Appendix A
112
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
11: m3/h
12: Kg/s
13: Kg/Min
14: Kg/h
15~21: Reserved
P19.01
Displayed
decimal
places
0~4
3
P19.02
Max. PID2
reference
0.001~65.535
3 decimal places, the decimal place changes along
with P19.01
1.000
P19.03
Upper limit
of PID2
reference
P19.04~P19.02
1.000
P19.04
Lower limit
of PID2
reference
0.001~P19.03
0.100
P19.05
PID2
reference
source
0: P19.06
1: AI1
2: AI2
3: AI3
4: HDI
5: Multi-step speed
6: MODBUS
7: Profibus-DP/CANopen/BACnet/Devicenet
8: Ethernet
9: Reserved
0
P19.06
PID2
keypad
reference 2
P19.04~P19.03
0.100
P19.07
PID2
reference
ACC/DEC
time
0.0~1000.0s
0.0s