Goodrive300-16 special inverter for HVAC Appendix A
114
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P19.20
Integral
separation
threshold
0.0~200.0%
200.0%
P19.21
Differential
filter times
0~60
4
P19.22
PID2 output
gain
0.30~3.00
1.00
P19.23
PID2 output
filter time
0.000~60.000s
0.000s
P19.24
PID2
control
mode
0: Feedback differential processing
1: Deviation differential processing
0
P19.25
PID2 start
feedback
0.001~P19.02
3 decimal places, the decimal place changes along
with P19.01
P19.29=1, if the output feature is positive and the
feedback is smaller than P19.25, PID2 will start
automatically. If the output feature is negative and
the feedback is larger than P19.25, PID2 will start
automatically.
0.300
P19.26
PID2 start
delay time
0.0~300.0s
1.0s
P19.27
PID2 stop
feedback
0.001~P19.02
3 decimal places, the decimal place changes along
with P19.01
P19.29=1, if the output feature is positive and the
feedback is larger than P19.27, PID2 will stop
automatically. If the output feature is negative and
the feedback is smaller than P19.27, PID2 will stop
stop automatically.
0.700
P19.28
PID2 stop
delay time
0.0~300.0s
1.0s
P19.29
PID2
enabling
0: Invalid
1: Valid
0