Goodrive300-16 special inverter for HVAC Appendix A
117
Detailed instruction of parameters
month and
day when fire
enabled
Current time
when fire
enabled
P22 Group HVAC special function
0: Limited frequency running
1: Hibernation according to running frequency
2: Hibernation according to deviation
Hibernation
starting
frequency
P00.05~P00.04 (upper limit frequency)
Allow hibernation when the running frequency is
smaller than the value and the hold time is larger
than P22.04.
Hibernation
starting
deviation
0.0~30.0% (relative to Max. PID1 value)
when the output feature is positive, the feedback is
larger than reference, the actual deviation is larger
than the value and the hold time is larger than
P22.04. Allow hibernation when the output feature
is negative, the feedback is smaller than reference,
the actual deviation is larger than the value and the
hold time is larger than P22.04.
Hibernation
entry delay
time
PID1
reference
boost value
-100.0~100.0% (relative to PID1 reference)