Goodrive300-16 special inverter for HVAC Appendix A
122
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P22.33
Circulation
cycle of
power
frequency
motor
0.0~6000.0h
Automatic circulation among idle power frequency
motors, no circulation in the stage of adding or
reducing motors or hibernation, no circulation all
the time when setting to 0
0.0h
P22.34
Circulation
cycle of
variable
frequency
motor
0.0~6000.0h
Automatic circulation among idle variable
frequency motors, no circulation in the stage of
adding or reducing motors or hibernation, no
circulation all the time when setting to 0
0.0h
P22.35
Circulation
frequency
threshold
P00.05~P00.03
When the running frequency is larger than the
value, there will be no circulation for variable
frequency motors to protect water supply from big
changes of water pressure.
45.00Hz
P22.36
Contactor
switching-on
time
0.2~100.0s
Time from sending contactor switching-on
command to switching on actually, send the
inverter start command after delaying the time
0.5s
P22.37
Contactor
switching-off
time
0.2~100.0s
Time from sending contactor switching-off
command to switching off actually, connect to
power frequency after delaying the time
0.5s
P22.38
Switch
frequency
at manual
soft start
0.00~P00.03
For testing whether the motor works normally
50.00Hz
P22.39
Water level
signal input
of inlet
sump
0: No input
1: Digital input
2: AI1
3: AI2
0

Related product manuals