Goodrive300-16 special inverter for HVAC Commissioning guidelines
24
the hold time is larger than P22.04.
Hibernation starting
deviation
Relative to the maximum PID1 value
Allow hibernation only when the output
feature is positive, feedback is larger than
reference, the absolute value of the actual
deviation is larger than the value and the
hold time is larger than P22.04.
Allow hibernation only when the output
feature is negative, feedback is smaller
than reference, the absolute value of the
actual deviation is larger than the value
and the hold time is larger than P22.04.
Hibernation entry
delay time
Relative to PID1 reference
Used to avoid the case where the inverter
runs continuously when the running
frequency reaches the upper limit while
the feedback cannot reach the set value
after boost, the inverter will enter
hibernation immediately after boost time.
Hibernation waking
frequency
PID output directly starts superposition
from the frequency when waking up in
close loop.
Hibernation waking
deviation
Relative to the maximum PID1 value
Allow waking up only when the output
feature is positive, feedback is smaller
than reference, the absolute value of the
actual deviation is larger than the value
and the hold time is larger than P22.09.
Allow waking up only when the output
feature is negative, feedback is larger
than reference, the absolute value of the