EasyManua.ls Logo

INVT Goodrive 300-16 - Page 45

INVT Goodrive 300-16
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive300-16 special inverter for HVAC Appendix A
44
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
power off
P01.23
Start delay
time
0.0~60.0s
0.0s
P01.24
Delay time
of stop
speed
0.0~100.0s
0.0s
P01.25
0Hz output
selection
0: Output without voltage
1: Output with voltage
2: Output at DC braking current at stopping
1
P02 Group Motor 1
P02.01
Rated
power of
asynchrono
us motor 1
0.1~3000.0kW
Depend
on
model
P02.02
Rated
frequency
of
asynchrono
us motor 1
0.01Hz~P00.03 (Max. output frequency)
50.00Hz
P02.03
Rated
speed of
asynchrono
us motor 1
1~36000rpm
Depend
on
model
P02.04
Rated
voltage of
asynchrono
us motor 1
0~1200V
Depend
on
model
P02.05
Rated
current of
asynchrono
us motor 1
0.8~6000.0A
Depend
on
model
P02.06
Stator
resistor of
0.001~65.535Ω
Depend
on

Related product manuals