EasyManua.ls Logo

INVT Goodrive 300-16 - Page 9

INVT Goodrive 300-16
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive300-16 special inverter for HVAC Product overview
8
Function
Specification
PID function
2 sets of PID
Overload capability
G type: 150% of rated current: 60 seconds
180% of rated current: 10 seconds
200% of rated current: 1 second
P type: 120% of rated current: 60 seconds
Starting torque
0.3Hz 150% (sensorless vector control)
Protection function
More than 30 protection functions, including
overvoltage, overcurrent, overheating and phase
loss
Peripheral
interface
Analog input
2 0~10V/0~20mA and 1 -10~10V
Analog output
2 0~10V/0~20mA
Digital input
8 common inputs, the Max. frequency: 1kHz,
selectable PNP/NPN
1 high speed input, the Max. frequency: 50kHz
Digital output
2 programmable relay outputs, NO and NC;
1 high speed pulse output
Communication
Standard 485 interface, available RTU protocol
Communication
extension interface
Available Profibus DP, DeviceNet, BACnet and
CANopen
Relay extension card
6 programmable relay outputs, NO
Others
Mountable method
Wall and flange mountable
Temperature of the
running environment
-25~55, derate above 40, If temperature is
above 40, derate 1% for every additional 1.
Average non-fault
time
2 years (25 ambient temperature)
Protective degree
IP20
Safety
Meet CE requirements
Cooling
Forced air-cooling
DC reactor
Unavailable for 30kW and below, available for 37kW
above
EMC filter
Built-in C3 filters: meet the degree requirement of
IEC61800-3 C3

Related product manuals