Goodrive300-16 special inverter for HVAC Product overview
8
G type: 150% of rated current: 60 seconds
180% of rated current: 10 seconds
200% of rated current: 1 second
P type: 120% of rated current: 60 seconds
0.3Hz 150% (sensorless vector control)
More than 30 protection functions, including
overvoltage, overcurrent, overheating and phase
loss
2 0~10V/0~20mA and 1 -10~10V
8 common inputs, the Max. frequency: 1kHz,
selectable PNP/NPN
1 high speed input, the Max. frequency: 50kHz
2 programmable relay outputs, NO and NC;
1 high speed pulse output
Standard 485 interface, available RTU protocol
Communication
extension interface
Available Profibus DP, DeviceNet, BACnet and
CANopen
6 programmable relay outputs, NO
Wall and flange mountable
Temperature of the
running environment
-25~55℃, derate above 40℃, If temperature is
above 40℃, derate 1% for every additional 1℃.
2 years (25℃ ambient temperature)
Unavailable for 30kW and below, available for 37kW
above
Built-in C3 filters: meet the degree requirement of
IEC61800-3 C3