Goodrive35 Series Closed-loop Vector Control VFD  Fault tracking 
209 
8.6.6 Overheat of the VFD 
VFD overheating
Clean the heat sink and 
improve the condition
Reduce the carrier 
frequency
If it is a VFD fault, please 
contact with our 
company
If the it is a VFD fault, 
please contact with our 
company
Decrease the load and 
increase the capacity of 
the VFD
Add heat-releasing 
device or derate the VFD 
Check if the ambient 
temperature is too 
high
Check if the carrier 
frequency is too high
Check if the heat sink 
is jammed
Check if there is 
abnormal noise to the 
fan of the VFD
Yes
No 
Yes
No 
Yes
No 
Yes
No 
Yes 
No 
Check if the load is too heavy 
Or the capacity of the VFD
 is too low
 
8.6.7 Motor stall during ACC   
Speed loss occurs to the 
VFD during ACC
Check if the ACC time 
is too short
If it is a VFD fault or 
interference, please 
contact with our 
company
Overcurrent 
If it is a VFD fault or 
interference, please 
contact with our 
company
Check if it performs 
parameter  autotune
Modify the torque boost 
Check if the torque 
boost is too high 
过电流
Check if the motor is 
special 
Reduce the inertia of the 
load and increase the 
capacity of the VFD
Check if it is V/F 
control 
Contact with our 
company
Check if the load 
torque is too big
Thicken the motor cables and shorten 
the configuration distance and adjust the 
voltage of the reactor
Check if the load and 
inertia is too big
Increase the ACC time 
Check if the voltage between the 
terminals is among the range 
Reduce the torque of the 
load and increase the 
capacity of the VFD
Yes 
No 
Yes 
No 
Yes 
No 
Yes 
No 
Yes 
No 
Yes 
No 
Yes 
No 
Yes 
No