Goodrive35 Series Closed-loop Vector Control VFD  Communication protocol 
233 
The exception response code  86H  (generated based on the  MSB "1" of the write  command 06H) 
indicates that it is an exception response to the write command (06H). The error code is 04H. From 
the  preceding table,  we  can  see  that  it  indicates the  error  "Operation failure", which means  "The 
parameter is set to an invalid value in the write operation". 
10.4.8 Example of writing and reading   
For details about the formats of the read and write commands, see sections 10.4.1 and 10.4.2.   
10.4.8.1 Example of reading command 03H   
Example 1: Read state word 1 of the VFD whose address is 01H. From the table of other function 
parameters, we can see that the parameter address of state word 1 of the VFD is 2100H.   
The read command transmitted to the VFD is as follows:   
Read
command
 
VFD
address
CRC check
 
Parameter
address
 
Data quantity 
01 03 21 00 00 01 8E 36
 
Assume that the following response is returned: 
Read
command
 
Number 
of bytes
Data content 
CRC check 
VFD
address
01 03 02 00 03 F8 45
 
The data content returned by the VFD is 0003H, which indicates that the VFD is in the stopped state. 
Example 2: View information about the VFD whose address is 03H, including "Type of current fault" 
(P07.27) to  "Type of  last  but four fault" (P07.32) of  which the  parameter addresses are 071BH to 
0720H (contiguous 6 parameter addresses starting from 071BH). 
The command transmitted to the VFD is as follows: 
VFD
address
Read
command
 
Start
address
 
6 parameters in total
CRC check
 
03 03 07 1B 00 06 B5 59
 
Assume that the following response is returned: 
VFD
address
Read
command
 
Number of 
bytes
  Type of
last fault
Type of 
current fault
 
 
Type of last 
but one fault
CRC check Type of last
but two fault
Type of last
but three fault
Type of last
but four fault
03 03 0C 00 23 00 23 00 23 00 23 00 2300 23 5F D2
 
From the returned data, we can see that all the fault types are 0023H, that is, 35 in the decimal form, 
which means the maladjustment fault (STo). 
10.4.8.2 Example of writing command 06H 
Example 1: Set the VFD whose address is 03H to  be forward running. Refer to the table of other 
function parameters, the address of "Communication-based control command" is 2000H, and 0001H 
indicates forward running, as shown in the following figure.