EasyManua.ls Logo

INVT Goodrive170-PV Series - Page 44

INVT Goodrive170-PV Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive170-PV Series Solar Pump Inverter Function parameter list
-40-
Function
code
Name
Description
Default
Modify
pre-alarm (A-tL) with a delay specified by
P15.16 and then sleeps. In empty-water
alarm state, the empty-water signal is
invalid, the system clears the empty-water
alarm with a delay specified by P15.17 and
then re-enters the running state.
P15.14
Full-water
level delay
010000s
Time setting on full-water level delay. (This
parameter is still valid for digital full-water
signal.)
5s
P15.15
Full-water
level
wake-up
delay
010000s
Time setting on full-water level wake-up
delay. (This parameter is still valid for
digital full-water signal.)
20s
P15.16
Empty-wat
er level
delay
010000s
Time setting on empty-water level delay.
(This parameter is still valid for digital
empty-water signal.)
5s
P15.17
Empty-wat
er level
wake-up
delay
010000s
Time setting on empty-water level wake-up
delay. (This parameter is still valid for
digital empty-water signal.)
20s
P15.18
Hydraulic
probe
damage
0.0100.0%
If P15.18 is 0.0%, it indicates P15.18 is
invalid.
If P15.18 is not 0.0%, when the detected
water level control analog signal is greater
than the value set in P15.18, the (tSF) fault
is reported and the inverter stops.
0.0%
P15.19
Water
pump run
time in
underload
state
0.01000.0s
Duration in which the water pump runs in
underload state. In continuous underload
condition, the underload alarm (A-LL) is
reported when the run time is reached.
60.0s
P15.20
Current
detection
value at
0.0%: Automatic detection on underload
0.1100.0%
The value 0.0% indicates it is determined
00.00%

Related product manuals