Goodrive350-19 series VFD Function parameter list
- 268 -
Y,
RO1, RO2
Output frequency
Set
frequency
Detection amplitude
Time t
Time t
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
Enable energy-
consumption
brake
0x00–0x11
Ones place:
0: Disable energy-consumption
1: Enable energy-consumption
Tens place:
0: Disable braking short circuit protection
1: Enable braking short circuit protection
There is no braking short circuit protection for the
22kW and lower VFD models by default.
Energy-
consumption
brake threshold
voltage
Set the starting bus voltage of
energy-consumption brake, adjust this value
properly can brake the load effectively. The default
value will change with the change of voltage class.
Setting range: 200.0–2000.0V
220V
voltage:
380.0V;
380V
voltage:
700.0V;
660V
voltage:
1120.0V
Running mode of
cooling fan
0: Common running mode
1: The fan keeps running after power up