EasyManua.ls Logo

INVT Goodrive350-19 Series - Page 276

INVT Goodrive350-19 Series
540 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350-19 series VFD Function parameter list
- 269 -
Function
code
Name
Description
Default
value
Modify
2: Running mode 2
P08.40
PWM selection
0x00000x1121
Ones: PWM mode
0: PWM mode 1, 3PH and 2PH modulation
1: PWM mode 2, 3PH modulation
Tens: PWM low-speed carrier wave limit
0: Limit low-speed carrier wave, limit mode 1
1: Limit low-speed carrier wave, limit mode 2
2: No limit on low-speed carrier
Hundreds: Reserved
Thousands: PWM loading mode
0: Interrupt loading
1: Normal loading
0x1101
P08.41
Overmodulation
selection
0x000x11
Ones
0: Overmodulation is invalid
1: Overmodulation is valid
Tens
0: Mild overmodulation
1: Deepened overmodulation
Hundreds: carrier frequency limit selection
0: Limit
1: Not limit
Thousands: Output voltage compensation
selection
0: Not compensate
1: Compensate
01
P08.42
Reserved
0001223
0x0003

Table of Contents

Related product manuals