0x000–0x221
Ones: Frequency control selection
0: UP/DOWN terminal setup is valid
1: UP/DOWN terminal setup is invalid
Tens: Frequency control selection
0: Valid only when P00.06=0 or P00.07=0
1: All frequency modes are valid
2: Invalid for multi-step speed when multi-step
speed takes priority
Hundreds: Action selection during stop
0: Valid
1: Valid during running, clear after stop
2: Valid during running, clear after receiving stop
command
0x000–0x111
Ones: Action selection for frequency setup (by
keypad digits) during power down
0: Save during power down
1: Zero out during power down
Tens: Action selection for frequency setup (by
MODBUS) during power down