EasyManua.ls Logo

INVT Goodrive350-19 Series - Page 283

INVT Goodrive350-19 Series
540 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350-19 series VFD Function parameter list
- 276 -
Function
code
Name
Description
Default
value
Modify
Reference
Deviation
limit
Feedback
Output
frequency f
Time t
Time t
P09.09
Upper limit value
of PID output
These two function codes are used to set the
upper/lower limit value of PID regulator.
100.0% corresponds to Max. output frequency
(P00.03) or max. voltage (P04.31)
Setting range of P09.09: P09.10100.0%
Setting range of P09.10: -100.0%P09.09
100.0%
P09.10
Lower limit value
of PID output
0.0%
P09.11
Feedback offline
detection value
Set PID feedback offline detection value, when the
detection value is no more than the feedback
offline detection value, and the duration exceeds
the value set in P09.12, the VFD will report "PID
feedback offline fault", and keypad displays PIDE.
T
Output frequency
t1 t2
P09.11
t1T2, so the VFD
continues running
t2=P09.12
Running
Fault output PIDE
PIDE
Setting range of P09.11: 0.0100.0%
Setting range of P09.12: 0.03600.0s
0.0%
P09.12
Feedback offline
detection time
1.0s
P09.13
PID control
selection
0x00000x1111
Ones:
0: Continue integral control after the frequency
0x0001

Table of Contents

Related product manuals