Goodrive350-19 series VFD Function parameter list
- 277 -
Function
code
Name
Description
Default
value
Modify
reaches upper/lower limit
1: Stop integral control after the frequency reaches
upper/lower limit
Tens:
0: The Same as the main reference direction
1: Contrary to the main reference direction
Hundreds:
0: Limit based on the max. frequency
1: Limit based on A frequency
Thousands:
0: A+B frequency, acceleration /deceleration of
main reference A frequency source buffering is
invalid
1: A+B frequency, acceleration/ deceleration of
main reference A frequency source buffering is
valid, acceleration and deceleration are
determined by P08.04 (acceleration time 4).
P09.14
Low-frequency
proportional gain
(Kp)
0.00100.00
Low-frequency switching point: 5.00Hz,
high-frequency switching point: 10.00Hz (P09.04
corresponds to high-frequency parameter), and
the middle is the linear interpolation between these
two points
1.00
P09.15
Acceleration/
deceleration time
of PID command
0.01000.0s
0.0s
P09.16
Filter time of PID
output
0.00010.000s
0.000s
P09.18
Low frequency
integral time
0.0010.00s
0.90s