Goodrive350-19 series VFD Function parameter list
- 278 -
Low frequency
differential time
Low frequency
point of switching
PID parameters
High frequency
point of switching
PID parameters
7.2.11 P10 Simple PLC and multi-step speed control
0: Stop after running once; the VFD stops
automatically after running for one cycle, and it
can be started only after receiving running
command.
1: Keep running in the final value after running
once; The VFD keeps the running frequency and
direction of the last section after a single cycle.
2: Cyclic running; the VFD enters the next cycle
after completing one cycle until receiving stop
command and stops.
Simple PLC
memory selection
0: No memory after power down
1: Memory after power down; PLC memories its
running stage and running frequency before power
down.
Setting range of the frequency in 0
th
–15
th
sections
are -100.0–100.0%, 100% corresponds to Max.
output frequency P00.03.
Setting range of the running time in 0
th
–15
th
sections are 0.0–6553.5s (min), the time unit is