determined by P10.37.
When simple PLC operation is selected, it is
required to set P10.02–P10.33 to determine the
running frequency and running time of each
section.
Note: The symbol of multi-step speed determines
the running direction of simple PLC, and the
negative value means reverse running.
When selecting multi-step speed running, the
multi-step speed is within the range of
-fmax–fmax, and it can be set continuously. The
start/stop of multi-step stop is also determined by
P00.01.
Goodrive350-19 series VFD can set 16-step
speed, which are set by combined codes of
multi-step terminals 1–4 (set by S terminal,
correspond to function code P05.01–P05.06) and
correspond to multi-step speed 0 to multi-step
speed 15.