During accelerated running, as the load is too
large, the actual acceleration rate of motor is lower
than that of output frequency, if no measures are
taken, the VFD may trip due to overcurrent during
acceleration.
0x00–0x21
Ones: Hardware and software current-limit action
selection
0: Invalid
1: Always valid
Tens: Hardware current-limit overload alarm
selection
0: OL2 is valid
1: OL2 is invalid
2: Reserved
Note: It can be modified only after P11.26 is 1
indicating special functions are enabled.
Current-limit protection function detects output
current during running, and compares it with the