EasyManua.ls Logo

INVT Goodrive350-19 Series - Page 291

INVT Goodrive350-19 Series
540 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350-19 series VFD Function parameter list
- 284 -
Function
code
Name
Description
Default
value
Modify
P11.07
Frequency-drop
rate during current
limit
current-limit level defined by P11.06, if it exceeds
the current-limit level, the VFD will run at stable
frequency during accelerated running, or run in
decreased frequency during constant-speed
running; if it exceeds the current-limit level
continuously, the VFD output frequency will drop
continuously until reaching lower limit frequency.
When the output current is detected to be lower
than the current-limit level again, it will continue
accelerated running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
Setting range of P11.06: 50.0250.0%
Setting range of P11.07: 0.0050.00Hz/s
10.00
Hz/s
P11.08
VFD or motor
overload/underloa
d pre-alarm
If the VFD or motor output current is larger than
the overload pre-alarm detection level (P11.09),
and the duration exceeds the overload pre-alarm
detection time (P11.10), overload pre-alarm signal
will be outputted.
0x0000
P11.09
Overload
pre-alarm
detection level
150%
P11.10
Overload
pre-alarm
detection time
1.00s

Table of Contents

Related product manuals