Setting range of P11.08:
Enable and define overload pre-alarm function of
the VFD and motor
Setting range: 0x000–0x131
Ones:
0: Motor overload/underload pre-alarm, relative to
rated motor current;
1: VFD overload/underload pre-alarm, relative to
rated VFD current.
Tens:
0: The VFD continues running after
overload/underload alarm;
1: The VFD continues running after underload
alarm, and stops running after overload fault;
2: The VFD continues running after overload
alarm, and stops running after underload fault;
3: The VFD stops running after overload/underload
fault.
Hundreds:
0: Always detect
1: Detect during constant-speed running
Setting range of P11.09: P11.11–200%