Goodrive350-19 series VFD Function parameter list
- 286 -
Setting range of P11.10: 0.01–3600.00s
Underload
pre-alarm
detection level
Underload pre-alarm signal will be outputted if the
output current of the VFD or motor is lower than
underload pre-alarm detection level (P11.11), and
the duration exceeds underload pre-alarm
detection time (P11.12).
Setting range of P11.11: 0– P11.09
Setting range of P11.12: 0.01–360.00s
Underload
pre-alarm
detection time
Fault output
terminal action
during fault
This function code is used to set the action of fault
output terminals during undervoltage and fault
reset.
0x00–0x11
Ones:
0: Act during undervoltage fault
1: Do not act during undervoltage fault
Tens:
0: Act during fault reset
1: Do not act during fault reset
Speed deviation
detection value
0.0–50.0%
This parameter is used to set the speed deviation
detection value.
Speed deviation
detection time
This parameter is used to set the speed deviation
detection time. If P11.14 is set to a non-zero value,
and the speed deviation is greater than the value
of P11.14, which lasts the time specified by
P11.15, the speed deviation fault dEu is reported.
Note: Speed deviation protection will be invalid if
P11.15 is set to 0.0.