M720 pH/ORP Controller Owner’s Manual
iii. Use Up/Down buon to increase/decrease Over
Timer
iv. When nished, press Mode buon to connue
4. The Over Timer is interlocked with the Dose Time
selecon.
i. If the Dose Time is set to a med cycle, the Over
Timer will count med feed cycles. Every me the
set level is reached the mer will reset its count. If
the preset cycle is reached, the pH digital display will
ash, and the pH output relay will de-energize. The
controller must be reset manually by cycling out of
and back into Auto mode using the mode buon.
(Default: 60 cycles)
ii. If the Dose Time is set to a connuous feed mode,
the Over Timer will count in minutes. (Default: 60
minutes)
5. When the Dose Time is changed from either med or
connuous feed, the Over Timer is reset to Default.
e. High Alert - Default: 8.0 pH
1. Default: 8.0 pH
2. Selectable range: OFF, 7.5 pH to 8.4 pH (acid feed). A
high alert will occur if the pH level remains above the
High Alert level for 10 connuous minutes, and will
automacally turn o the High Alert when the pH level
falls below the high alert level for 1 connuous minute.
During High Alert, the pH dose output will be disabled.
3. Changing High Alert seng
i. Press Mode buon to enter pH standby
ii. Press and hold Mode buon and then press Set Level
buon (red pH alert LED will come on) release both
buons. You are now in Set Alerts mode.
iii. Press Set Level buon again to display current High
Alert