ii. Press and hold Mode buon and then press Set Level
buon (red ORP alert LED will come on) release both
buons. You are now in Set Alerts mode.
iii. Press Set Level buon again to display current High
Alert
iv. Use Up/Down buon to increase/decrease ORP High
Alert
v. When nished, press Mode buon to connue
e. Low Alert
1. Default: 100 mV
2. Selectable range: OFF, 100 mV to 640 mV. A low alert
will occur if the ORP level remains below the Low Alert
level for 10 connuous minutes, and will automacally
turn o the Low Alert when the ORP level rises above
the low alert level for 1 connuous minute. During Low
Alert, the ORP1 dose output will be disabled.
3. Changing Low Alert seng
i. Press Mode buon to enter ORP standby
ii. Press and hold Mode buon and then press Set Level
buon (red ORP alert LED will come on) release both
buons. You are now in Set Alerts mode.
iii. Press Dose Time buon to display current Low Alert
iv. Use Up/Down buon to increase/decrease ORP Low
Alert
v. When nished, press Mode buon to connue
f. pH Cal disabled
5. Flow
a. The controller and ow cell are shipped pre-mounted to a
small (16” x 12”) or large (24” x 19”) ABS plasc board. The
integrated ow switch is pre-wired to the controller.
21
M720 pH/ORP Controller Owners Manual