M920 & M920W pH/Dual ORP Controller Owner’s Manual
18
g. While sll in the pH standby mode, press the pH Cal pushbuon
to calibrate the reading to the value observed through the
manual tesng of the water. Note:Alwayscalibrateusingwater
fromthesampleportoftheowcell.
h. Press the Mode pushbuon momentarily to place the controller
in ORP1 standby mode. The yellow ORP1 standby LED will
illuminate. Select the desired ORP1 set level and dose me
(connuous or med). Please call us at 877-693-6903 for
assistance with inial sengs.
i. Press the Mode pushbuon momentarily unl the red Auto LED
is illuminated. Note: If pH level in the pool is at desired set level
andchlorine/brominelevelisatdesiredPPMlevelinthepool,
then the ORP set level should be the same as the current ORP
readingwheninAutoMode.
2. Shutdown
Note:EachmetheModepushbuonismomentarilypressed,the
modewillcyclefromAutotopHtoORP1toORP2,Temp,andthen
return to Auto mode.
a. Press the Mode pushbuon momentarily to place the controller
in pH standby mode. The green pH standby LED will illuminate,
and both the pH and ORP digital displays will show dashes.
b. Press and hold the Mode pushbuon for 2 seconds unl both
the pH and ORP digital displays read OFF.
c. Release the Mode pushbuon. The M920 controller will turn
o, and the digital displays and funcon LEDs will go blank. The
green Flow LED will be illuminated if water is owing through
the ow cell.
C. Modes and Adjustments
1. Auto
a. This is the normal operaonal mode of the M920 controller.
b. The controller allows full operaon and monitoring of both pH
and ORP levels.
c. No funcon pushbuons are operaonal in this mode.