M920 & M920W pH/Dual ORP Controller Owner’s Manual
21
g. pH Cal
1. Use to adjust pH to manually tested value.
2. Maximum increase/decrease is 0.9 pH within the 6.0 to 8.4
display window.
3. ORP1 standby
Note:Whileinthismode,theyellowORP1standbyLEDwillilluminate,
boththepHandORPdigitaldisplayswillshowdashes,andallAuto
funconswillbedisabled.UsetheUporDownarrowbuonstothe
letoincreaseordecreasethefunconvalue.
a. Set Level
1. Default: 650 mV
2. Selectable range: 400 mV to 900 mV (in 5 mV increments)
b. Dose Time
1. Default: 10-second ORP feed relay energized and 5 minutes
ORP feed relay de-energized (med dose me). In the med
dose cycle mode, the dose LED will ash while dosing, and
will illuminate steadily during the delay poron of the med
cycle. In connuous dose mode, the dose LED will ash while
dosing, and dosing will connue unl ORP is 10 mV above Set
Level.
2. Selectable range: OFF, CON (connuous), and Timed
(10 to 900 seconds ON)
c. Delay Time
1. Default: Delay me of 5 minutes between feed cycles (med
feed only). Aer dose me, the controller will wait (delay) for
the specied minutes before checking the current level and
dosing again if necessary.
2. Selectable range: 1 - 99 minutes.
d. Over Timer
1. Default: ON. The Over Timer does not automacally reset. It
must be reset by turning the controller o, then on.
2. The Over Timer is interlocked with the Dose Time selecon.