M920 & M920W pH/Dual ORP Controller Owner’s Manual
23
a. Set Level
1. Default: 640 mV
2. Selectable range: 400 mV to 890 mV (in 5 mV increments),
cannot be set for less than 10 mV below the ORP1 set level.
b. Dose Time
1. Default: OFF. In the med dose cycle mode, the dose LED will
ash while dosing and illuminate steadily during the delay
poron of the med cycle. In connuous dose mode, the
dose LED will ash while dosing, and dosing will connue
unl ORP is 10 mV above Set Level.
2. Selectable range: OFF, CON (connuous), and Timed
(10 to 900 seconds ON)
c. Delay Time
1. Default: OFF. Delay me of 5 minutes between feed cycles
(med feed only). Aer dose me, the controller will wait
(delay) for the specied minutes before checking the current
level and dosing again if necessary.
2. Selectable range: 1 - 99 minutes.
d. Over Timer
1. Default: ON. The Over Timer does not automacally reset. It
must be reset by using the mode buon to cycle out of auto
and then back to auto mode.
2. The Overfeed mer is interlocked with the Dose Time
selecon.
3. If the Dose Time is set to a med cycle, the Over Timer will
count med feed cycles. Every me the set level is reached
the Over Timer will reset the count. If the set (default is 60
cycles) Over Timer cycle is reached, the ORP2 output relay
will de-energize. ORP2 will not ash ORP digital display if
ORP2 overfeed occurs).
4. Selectable range in med feed: OFF, 20 – 100 feed cycles.
Selectable range in connuous feed: OFF, 20 – 180 minutes.
When the Dose Time is changed from either med or con-
nuous feed, the Over Timer is reset to Default.