© IS Technologies Co., Ltd. PAGE 40 / 41
ULM-1000C Menu List
Program No. Menu Range Factory Set Note
Application
P01 Measurement
1. Level
2. Distance
3. Space
Distance
P02 Unit
1. meter
2. feet
meter
P03 Display
1. Level
2. mA
3. %
level
P04 Bottom Distance 0. 000 ~7.000m 6.000m
P05 Dead Zone 0. 300 ~ 6.000m 0.300m
Current
Output
P06 4mA Output 0 ~ 7.000m 0
P07 20mA Output 0 ~ 7.000m 6.000m
P08 Error
1. 3.8mA
2. Hold
3. 22mA
22mA
P09 mA Fail-safe Time 20-900sec 300sec
Compensation
P10 Damping Rate 0.01-100/min 1m/min
P11 Threshold 3(Low) – 15(High) 3(Low)
P12 Output Power 1(Weak) – 4(Strong) 2
P13 Sound Velocity 150-500 331.5m/s
P14
Vapor Temperature
Compensation
-
200 ~ 200
60cm/°c
P15
Detection
Algorithm
1. Automatic
2. Effective only for the first
signal
Automatic
P16 Detection Target
1. Liquid
2. Bubble Liquid
3. Solid
4. Powder
Liquid
Output
Simulation
P17 Simulation 0.000-7.000 3.000m
Password P18 Password 0-9999 0