EasyManua.ls Logo

ISA T 2000 - Page 79

Default Icon
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC. MIE11110 Rev. 5
Page
79
of
110
B) Input connection:
- N. 1 cable for low voltage measurement connection, shielded, 4
m long, for the 10 V measurement, plus N. 2 Clamps to connect
the voltage measurement.
The test is performed as follows.
- First of all, move the tap changer all the way to the starting
position: this will be recorded as test number one.
- Select the base time of the recording, as a function of the
nominal selection time.
- Start the test and generate a current of one or two amps (if
possible). While you are generating, current, voltage and winding
plus tap contact resistance are displayed.
- Set the resistance trigger level to a value 1.5 to two times
greater than the displayed resistance.
- When you have defined the trigger level, the instrument stays
in the "trig mode", and waits until a resistance greater than the
trigger level is measured. Once triggered, the instrument shows
the resistance diagram on the display. Note that the vertical axis
is autoranging; so, for the measurement of the limiting resistor,
take into account the measurement of the winding resistance.
- Save the result, then, before performing the next test, change
the test number high left on the screen.
- Continue the same way until the stop position of the tap
changer has been reached.
- The Load Tap Changer fault is easily detected: if, at any
moment, the contact is lost, the resistance grows to infinity.
The resistance waveform changes as a function of the parasitic
transformer impedance and of the selection time. In the example,
the default of 50 ms per division covers a total time of 300 ms,
and there is no effect of the parasitic impedance.
The parasitic impedance is expressed by the parameter X/R, that
is one of the characteristic parameters of the transformer. The L/R
time constant of our test is related to the X/R parameter by the
following relationship:
L/R = (R/X) / 314
The resistance waveform of the example can be observed only if
L/R is small (less than 10%) of the selection time; otherwise, the

Related product manuals