FIRSTSTEPS
22 Measuringcentres
MC320,MC330,MC350&MC350H‐User’sManua
Current
Voltage
1A 5A 50A 100A 1000A
110V ‐1(100mWh) 0(1Wh) 1(10Wh) 1(10Wh) 2(100Wh)
230V 0(1Wh) 0(1Wh) 1(10Wh) 2(100Wh) 3(1kWh)
1000V 0(1Wh) 1(10Wh) 2(100Wh) 3(1kWh) 4(10kWh)
30kV 2(100Wh) 2(100Wh) 3(1kWh) 4(10kWh) 4*(10kWh)
*‐Counterdivider(MiQen2.xandabove‐IndividualCounterResolution)shouldbeatleast100
DEVICEADDRESS
SetMODBUSaddressforthedevice.Defaultaddressis33.
BITSPERSECOND
Setcommunicationrate.Defaultrateis115200b/s.
PARITY
Setcommunicationparity.DefaultvalueisNone.
STOPBIT
Setcommunicationstopbits.Defaultvalueis2.
Displayofdeviceinfo
Amenuisdividedintoseveralsubmenuswithdataandinformationaboutdevice:
Welcomescreen
Information
Meaningoficons
Welcomescreen
Whenenteringtheinformationmenu,awelcomescreenisdisplayedonLCDshowingtypedesignationandname
ofmeasuringcentre.
MainmenuInfoOK
Information
DataonadevicearecollectedintheInformationmenu.Theyincludeaserialnumber,a softwareversion,a
hardwareversion,dateofmanufactureandanumberofoperationalhoursindays,hoursandminutes.
MainmenuInfoOK
MainmenuInfoOK
Meaningoficons
Allpossibleiconswiththeirmeaningaredisplayed.
MainmenuInfoOK
ExampleofdisplayoficonswiththeirmeaningwithoutactiveiconsandatlockedMC:
Afterautomatic
passwordactivation