APPENDIXA:MODBUSPROTOCOL
Measuringcentres
MC320,MC330,MC350&MC350H ‐ User’sManua
55
Parameter Type
MC7x0RMComp. MI71x0RMComp.
Start End Start End
CounterE1 T3 30406 30407 30010 30011
CounterE2 T3 30408 30409 30012 30013
CounterE3 T3 30410 30411 30014 30015
CounterE4 T3 30412 30413 30016 30017
Activetariff T1 30405 30133
InternalTemperature T17 30181 30128
Registertableforthenormalizedactualmeasurements
Parameter
MODBUS
100%value
Register Type
VoltageU
1
30801 T16 Un
VoltageU
2
30802 T16 Un
VoltageU
3
30803 T16 Un
AveragephaseVoltageU
~
30804 T16 Un
PhasetophasevoltageU
12
30805 T16 Un
PhasetophasevoltageU
23
30806 T16 Un
PhasetophasevoltageU
31
30807 T16 Un
Average phase to phase Voltage
30808 T16 Un
CurrentI
1
30809 T16 In
CurrentI
2
30810 T16 In
CurrentI
3
30811 T16 In
TotalCurrentI 30812 T16 It
NeutralcurrentIn 30813 T16 In
AverageCurrentI
~
30815 T16 In
RealPowerP
1
30816 T17 Pn
RealPowerP
2
30817 T17 Pn
RealPowerP
3
30818 T17 Pn
TotalRealPowerP 30819 T17 Pt
ReactivePowerQ
1
30820 T17 Pn
ReactivePowerQ
2
30821 T17 Pn
ReactivePowerQ
3
30822 T17 Pn
TotalReactivePowerQ 30823 T17 Pt
ApparentPowerS
1
30824 T16 Pn
ApparentPowerS
2
30825 T16 Pn
ApparentPowerS
3
30826 T16 Pn
TotalApparentPowerS 30827 T16 Pt
PowerFactorPF
1
30828 T17 1
PowerFactorPF
2
30829 T17 1
PowerFactorPF
3
30830 T17 1
TotalPowerFactorPF 30831 T17 1
CAP/INDP.F.Phase1(PF
1
) 30832 T17 1
CAP/INDP.F.Phase2(PF
2
) 30833 T17 1
CAP/INDP.F.Phase3(PF
3
) 30834 T17 1
CAP/INDP.F.Total(PF
t
) 30835 T17 1