SETTINGS
Measuringcentres–M
320,MC330,MC350&MC350H ‐ User’sManual 31
Passwordandlanguage
Languagechangeispossiblewithoutpasswordinput.WhenlanguageischangedfromortoRussianorHebrew,
character transformation has to be taken in to account. Character transformation table (English or Russian
alphabet)isstatedbelow.
English A B C D E F G H I J K L M N O P
RSTUVWXYZ
Russian А Б В Г Д Е Ж З И Й К Л М Н O П P С Т У Ф Х Ц Ч Ш Щ
Energy‐counters
WARNING!
Beforemodification, allenergycounters should bereadorif energy valuesarestoredin
recorders,recordershouldbereadwithMiQensoftwareorstoredonMemorycardtoassure
dataconsistencyforthepast.
Aftermodificationofenergyparameters,theenergymeters(counters)shouldbereset.All
recordedmeasurementsfromthispointbackmighthavewrongvaluessotheyshouldnot
be transferred to any system for data acquisition and analysis. Data stored before
modificationshouldbeusedforthispurpose.
Activetariff
Whenactivetariffisset,oneofthetariffsisdefinedasactive;switchingbetweentariffsisdoneeitherwitha
tariffclockoratariffinput.Fortheoperationofthetariffclockotherparametersofthetariffclockthatare
accessibleonlyviacommunicationorMemorycardmustbesetcorrectly.
CommonEnergyExponent(CommonEnergyCounterResolution–MiQen
2.xandabove)
Commonenergyexponentdefinesminimalenergythatcanbedisplayedontheenergycounter.Onthebasisof
thisandacounterdivider,abasiccalculationprefixforenergyisdefined(−3is10
−3
Wh=mWh,4is10
4
Wh=10
kWh).Acommonenergyexponentalsoinfluencesinsettinganumberofimpulsesforenergyofpulseoutputor
alarmoutputfunctioningasanenergymeter.
Definecommonenergyexponentasrecommendedintablebelow,wherecounterdividerisatdefaultvalue10.
ValuesofprimaryvoltageandcurrentdetermineproperCommonenergyexponent.
InMiQensettingsoftwareversion2.xandabove,thissettingparameterisrenamedinCommonEnergyCounter
Resolution.Alsosettingvaluesarechangedtogiveuserbetterperspectiveofrepresentedvalue.
Intablebelow,newsettingvaluesarequotedinparenthesis.
Current
Voltage
1A 5A 50A 100A 1000A
110V ‐1(100mWh) 0(1Wh) 1(10Wh) 1(10Wh) 2(100Wh)
230V 0(1Wh) 0(1Wh) 1(10Wh) 2(100Wh) 3(1kWh)
1000V 0(1Wh) 1(10Wh) 2(100Wh) 3(1kWh) 4(10kWh)
30kV 2(100Wh) 2(100Wh) 3(1kWh) 4(10kWh) 4*(10kWh)
*‐Counterdivider(MiQen2.xandabove‐IndividualCounterResolution)shouldbeatleast100