MEASUREMENTS
44 Measuringcentres
MC320,MC330,MC350&MC350H‐User’sManua
Powerangle represents angle between first voltage harmonic andfirstcurrentharmonicforeachindividual
phase.Totalpowerangleiscalculatedfromtotalactiveandreactivepower(seeequationforTotalpowerangle,
chapterEquationsonpage72).Apositivesignshowsinductiveload,andanegativesignshowscapacitiveload.
Frequency
Networkfrequencyiscalculatedfromtimeperiodsofmeasuredvoltage.
MainmenuMeasurementsPresentvaluesFrequencyOK
Energy
Twowaysofenergydisplayareavailable:byindividualmetersandbytariffsforeachmeterseparately.Ata
displayofmeterenergybytariffs,thesumintheupperlinedependsonthetariffssetinthemeter.
MainmenuMeasurementsPresentvaluesEnergyOK
MDvalues
DisplayofMDvalues.
MainmenuMeasurementsPresentvaluesMDvaluesOK
THD‐Totalharmonicdistortion
THDiscalculatedforphasecurrents,phaseandphase−to−phasevoltagesandisexpressedaspercentofhigh
harmoniccomponentsregardingRMSvalueorrelativetofirstharmonic.
Instrumentusesmeasuringtechniqueofrealeffective(rms)valuethatassuresexactmeasurementswiththe
presenceofhighharmonicsupto32ndharmonic.
MainmenuMeasurementsPresentvaluesTHDOK
Customizedscreens
Adisplayofcustomizedscreensdependsonsettings.SeechapterSettingsofcustomizedscreensonpage29.
MainmenuMeasurementsPresentvaluesCustomOK
Overview
Itcombinesseveralmeasurementsoneachdisplayasthefollowingscreensaredisplayed:
ExplanationofmeasurementsforMC330atconnectionmode4u:
SCREEN1:
Currentphasemeasurements Currentphasemeasurements
U
AveragevoltageU
V P TotalactivepowerP
t
W
1 PhasevoltageU
1
V P1 ActivepowerP
1
W
2 PhasevoltageU
2
V P2 ActivepowerP
2
W
3 PhasevoltageU
3
V P3 ActivepowerP
3
W
I
AveragecurrentI
A Q TotalreactivepowerQ
t
var
1 CurrentI
1
A Q1 Reactivepower
1
var
2 CurrentI
2
A Q2 Reactivepower
1
var
3 CurrentI
3
A Q3 Reactivepower
1
var