EasyManua.ls Logo

iSMA CONTROLLI TP - Page 22

iSMA CONTROLLI TP
49 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
Modbus register: 41513;
BACnet object: BO55, property: Out Of Service;
Bit Name 0 1
1 Editable Not editable Editable (default)
2 Operating mode Changing offset Changing setpoint (default)
Table 13. Temperature setpoint configuration
SETPOINT_STEP: allows to set a temperature's setpoint step value. If the setpoint is
changed locally from the panel (using -/+ buttons), a single press of a button causes a
setpoint change with the step value stored in this register. The setpoint can be changed
in the range determined by setpoint limits stored in the SETPOINT_LOW_LIMIT and
SETPOINT_HIGH_LIMIT parameters.
The setpoint's step value is also automatically adjusted to the setpoint display precision. If
the bit 4 of the SETPOINT_CONFIGURATION register is true, the setpoint value is
displayed with one decimal place. In such case, the setpoint's step value is also adjusted
to one decimal place. The register contains a value multiplied by 10. The default value is
10 (1
o
C);
Modbus register: 41508
BACnet object: AV56, property: 4206;
EXIT_EDIT_TIME:allows to set the time after which edition of any editable parameter is
finished. The parameter is set in seconds. The default value is set to 5 seconds;
Modbus register: 40224
BACnet object: AO17, property: Present Value.
How to Change the Temperature Setpoint on the Touchscreen?
Short press + or - button to enter an edit mode (display should start blinking with
a current value);
Change the temperature setpoint value by steps set in the SETPOINT_STEP:
- button decreases the value (multiple times for long press);
+ button increases the value (multiple times for long press).
Reaching a limit value will be signaled with a double beep.
Device will automatically exit the edit mode after the time set in the
EXIT_EDIT_TIME expires from a last interaction.
LEDs
The device shows a difference between the EFFECTIVE_SETPOINT and
TEMPERATURE_SENSOR values on an LEDs ladder, which indicates the following:
For description of all bits of the SETPOINT_CONFIGURATION parameter seeUser
Interface Parameters.