Modbus
Address
Decimal
Address
Hex Register Name Access Default
Value
Value
Range
Description
41507 1506 0x5E
2
OFFSET_RANGE Read/
write
30 0-500 Limit offset value
41508 1507 0x5E
3
SETPOINT_STEP Read/
write
10 Setpoint step value
41513 1512 0x5E
8
SETPOINT_CONFIG
URATION
Read/
write
31 Setpoint configuration
of parameters: Visible,
Editable, Operating
mode, Setpoint display,
ThirdPointActive
Bit Name 0 1
0 VISIBLE Not visible Visible
(def)
Switches on/off a
temperature setpoint
visibility on a display
1 EDITABLE Not editable Editable
(def)
Activates/inactivates
editing of a temperature
setpoint locally on the
panel
2 OPERATING_MODE Changing offset Changi
ng
setpoin
t (def)
Switches between
changing offset or
setpoint
3 SETPOINT_DISPLAY Show/change offset Show/
change
effectiv
e
setpoin
t (def)
Switches between
changing offset or
setpoint
4 THIRD_POINT_ACTI
VE
No decimal Decimal
(def)
Activates/inactivates
decimal points
41601 1600 0x64
0
FAN_CURRENT_SPE
ED
Read/
write
0 Fan speed
41602 1601 0x64
1
FAN_MODE Read/
write
1 Fan mode
41603 1602 0x64
2
FAN_TYPE Read/
write
Fan type
41614 1613 0x64
D
FAN_CONFIGURATI
ON
Read/
write
2
Bit Name 0 1
1 EDITABLE Not editable Editable
(def)
Switches on/off editing
fan modes locally