TP Software User Manual
www.ismacontrolli.com
DMP253en | 1st Issue rev. 0 | 04/2022
BACnet
Type & ID
BACnet
Property
Decimal
Address
Hex Object
Name
Access Default
Value
Value
Range
Description
MSI1 Present
Value
28 0x1C SENSORS Read-
only
Informs
about built-in
sensors
AI1 Present
Value
200 0xC8 BACKLIGHT_LC
D
Read-
only
Actual display
illumination
value
AI2 Present
Value
201 0xC9 BACKLIGHT_KE
YPAD
Read-
only
Actual keypad
illumination
value
204 0xCC DEVICE_CONFI
GURATION
Read/
write
BO0 Present
Value
BUZZER_ACTIV
E
1 Activates (1)
or deactivates
(0) a buzzer
BO3 Present
Value
LCD_BACKLIG
HT_ACTIVE
1 Switches the
LCD
background
illumination
on (1)
BO4 Present
Value
KEYPAD_BACK
LIGHT_ACTIVE
1 Switches the
keypad
background
illumination
on (1)
BO5 Present
Value
CO2_ALARM_L
CD
Switches on
the function
of LCD
background
illumination
flashing when
CO2 alarm
occurs
BO6 Present
Value
CO2_ALARM_B
UZZER
Switches on a
buzzer when
the CO2
alarm occurs
BO63 Present
Value
CO2_ALARM_C
ONFIRM
1 Allows to
enable
confirmation
of the CO2
alarm with
any button of
the panel