25
8. Maintenance/Inspection
Error details on CBV30
8-1.
Error details
ErrordetailsonCBV30
■
When error signals have been released using CN2#1 (RUN / STOP), the MDR
instantly starts up when RUN is input.
■
When the power supply voltage is dropped to 8.5 V or less, an operation when
the power is shutdown or an unexpected operation may occur.
■
When releasing an error, switch ON→OFF→ON signals on CN2#1, and ON→
OFF→ON / OFF→ON→OFF signals on CN2#2, at intervals of 100 ms or more.
Errors can be checked by PWR (Green), ERR (Red), and signals from CN2#3.
LED details
Error details
:O N
:Blinking(1Hz):Blinking(6Hz)
:OFF
Type of error
(Normal operation)
Fuse blown
CN2#3
STTS
signal
Occurrence conditions
Error release
conditions
How to release error
Low voltage
Motor connector
unconnected
Motor lock
Back EMF error
Fuse meltdown
(Failure is detected after
1 second)
The driver card supply voltage
has been 15 V or less for 1
second, or decreases to 15 V
or less five times within 0.5
seconds.
・Motor cable connector
unconnected
・Motor cable connector
disconnected
Failure is detected if the
MDR does not rotate for
1 second
The MDR voltage has been
40 V or more for 2 seconds,
or it is 50 V or more
None (Replace the driver card.)
The driver card
supply voltage is
24V
±
10%
Correct connection
of the motor cable
Safety precautions
Advance preparation
Check ProductInstallation/Wiring
Maintenance/Inspection
Specifications Control/Operation
CBV30UserManual
■
Errors is also released when the power is OFF for 2.0 seconds or more.
−
−
ERR
(Red)
PWR
(Green)
MDR stop
Short circuit
brake
Output
Open
Open
Driver card
thermal error
Open
Open
Open
Open
⇔
⇔
⇔
・Input the signal of OFF →
ON to CN2#1 (RUN/STOP)
・Switch ON → OFF → ON
or OFF → ON → OFF on
CN2#2
The driver card (FET)
temperature has been 95ºC
or higher for 1 second
Resolve the
cause of lock error
The driver card
(FET) temperature
is 85ºC or lower
The MDR supply
voltage is 24V ±10%
The MDR internal
temperature is
110ºC or lower
Only the error signal will
be released by switching
the signal on CN2#2.
After the error has been
released, turn CN2#1 OFF
and ON to run and recover
the MDR.
*
Priority
ー
MDR
thermal error
Open
The MDR temperature is
110ºC
Short circuit
brake
Short circuit
brake
Coast
Short circuit
brake
Short circuit
brake
Short circuit
brake
×2
(3.5sec)
Current limiter
enabled
Output
Current limiter continues
for 3 seconds
1
4
5
2
3
6
7
**
* Activated when MDR is overloaded. Error signal is not discharged when current limiter is enabled.
LED indication is reset by disabling current limiter.
・ If multiple errors occur LED blinks on priority order.