ITW Dynatec Programming Page 5-35
V6 DCL Touch Screen Controller for Dynamelt M & D ASUs Revised 1/16
Pressure Zero Calibration
To go to this screen, press the General Settings button on the Settings Screen.
Item Description
1
Parameter Selection tabs
The Pressure Zero Calibration tab has been selected.
2
OK Button
Before calibrating the (optional) pressure transducers, all pumps must be in STOP mode and
the system must be fully depressurized. After taking the appropriate steps, confirm this by
pressing the OK button. You will then go to the Calibrating Screen.
2
1