Finding Installation
Position
Please find enough straight run pipe position. Normally, clamp-on
ultrasonic flowmeter need 10 Upstream and 5 Downstream diameters
straight pipe run. Ensure adequate straight pipe to ensure smooth laminar
flow. Accuracy will be affected if not enough straight pipe can be found.
Sensor Distance
Using the Sensor distance, measure the installation area on the pipe using
ruler. Remember that the area must be large enough for Mounting Track
installation with the sensor placement approximately in the center of the
track.
Remove Pipe Coating
and make install position
flat and clean
Please remove all pipe coatings and Use an abrasive to thoroughly clean
the area. This is essential for good Ultrasonic coupling.
Remove any coatings, and make this area
clean and flat for transducer mounting.