29
Technical data
11
General
Device dimensions (approx.) w=158.7 mm, h=108.5 mm, d=59.2 mm
(w=6.248 in, h=4.271 in, d=2.330 in)
Transport and storage
The following information applies to devices which are transported or stored
in the original packaging.
Temperature -40 °C to 70 °C (-40 °F to 158 °F)
Ambient conditions during operation
The device is intended for weatherproof, fixed installation and must be connected to the
ground wire connection! Protection class I in acc. with IEC 60536 (VDE 0106, Part 1).
Working temperature range 0 °C to 60 °C (32 °F to 140 °F)
Relative humidity < 95 % RH (without condensation)
Operating altitude 0 .. 2000 m (0 ...1.24 mi) max.
Pollution degree pollution degree 2
Mounting position any orientation
Ventilation not required; 3 W heat rejection