AC Power Supply
Installations of overvoltage category internally fused; install external fuse as
required by code
Protection of the supply voltage (fuse) 1 A @ 300 V AC
Overvoltage category II, degree 2
Operating range 90 .. 300 V AC (50-60 Hz)
Power consumption < 0.1 A @ 277 V AC (< 3W)
24 V DC Power Supply
Installations of overvoltage category internally fused; install external fuse as
required by code
Protection of the supply voltage (fuse) 0.5 A @ 24 V DC
Overvoltage category III, degree 2
Operating range 12 .. 24 V DC
Power consumption < 0.5 A @ 12 .. 24 V (< 3 W)
Terminal connection capacity (AC supply voltage)
Connectable conductors. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded 24-12 AWG / 0.205-3.31 mm²
Terminal pins, core end sheath slot screw type
Tightening torque 5.0 Lb-In / 0.56 Nm
Stripping length 5.5 mm (0.22 in) max.