Page: 93
FM-200® OPERATION, DESIGN, & SERVICE MANUAL
Revision F
Document # DOC102
Issued: February 1, 2009
Revised: 11-Nov-2011
40YE
FM-200® Surface Fire Requirements
Class A / Class C
Project: Date:
Hazard: Engineer:
Required FM-200® – UL (6.7% Concentration)
Volume
Design
Concentration
Factor @ 20°C
FM-200®
Weight
Sea Level
Altitude
Correction
Factor¹
Required Weight
FM-200®
m
3
x .5230 = kg x = kg
Storage Requirements
Required Weight FM-200® Number of Cylinders Weight per Cylinder
kg / = kg / cylinder²
Cylinders Main Cylinders Reserve
Qty
Series
Valve
Nominal
Cylinder
Size
Fill Capacity
Qty
Series
Valve
Nominal
Cylinder
Size
Fill Capacity
Minimum Maximum Minimum Maximum
Sv 40 lb
22 lbs
(10.0 kg)
43 lbs
(19.5 kg)
Mv 420 lb
211 lbs
(95.7 kg)
422 lbs
(191.4 kg)
Sv 80 lb
41 lbs
(18.6 kg)
81 lbs
(36.7 kg)
Lv 600 lb
304 lbs
(137.9 kg)
607 lbs
(275.3 kg)
Sv 130 lb
66 lbs
(29.9 kg)
131 lbs
(59.4 kg)
Lv 900 lb
455 lbs
(206.4 kg)
910 lbs
(412.8 kg)
Mv 250 lb
138 lbs
(62.6 kg)
274 lbs
(124.3 kg)
Lv 1000 lb
619 lbs
(280.8 kg)
1000 lbs
(453.6 kg)
1 See Table 3.1.4 for altitude correction factor.
2 Agent weights calculated using metric measurements must be converted to pounds and rounded UP to the nearest whole
pound when ordering for lling purposes. See Table B.2a for conversion factors.
B.2 Design Worksheet Metric
Required FM-200® – FM (7% Concentration)
Volume
Design
Concentration
Factor @ 20°C
FM-200®
Weight
Sea Level
Altitude
Correction
Factor¹
Required Weight
FM-200®
m
3
x .5483 = kg x = kg
Note: For other design concentrations or ambient temperatures use the formula located in section 3.2.
Appendix B

Table of Contents